KUNJI

Indoor AC High Voltage 12kv Load Switch Three-Phase Switchgear

stars, based on 0reviews
$200.00 piece
9999items available
Add inquiry cart Inquire Now

Product Description

Customized products can consult online customer service!


 FKN12-12D/T630-20 type indoor AC high-voltage load switch (referred to as FKN12-12D load switch) is a three-phase high-voltage switch with a rated voltage of 12KV and a rated frequency of 50Hz, which is used to divide the load current, closed-loop current, no-load transformer and cable charging current, and close the short-circuit current. Load switches equipped with ground switches can withstand short-circuit current.
Xh Indoor AC High Voltage 12kv Load Switch Three-Phase Switchgear Manufacturer
Xh Indoor AC High Voltage 12kv Load Switch Three-Phase Switchgear Manufacturer
F K N 12(1) A - 12(2) D / T 630 - 20
F:Load Switch                             
D:Ground Switch
K:Air Medium                             
T:Spring Mechanism
N:Indoor                                     
630:Rated Current(A)
12(1):Design Number                 
20:Rated Short-time Withstand Current(KA)
A:Derived Code                         
12(2):Rated Voltage(KV)    

F K R N 12(1) A - 12(2) D / T 125 - 31.5
F:Load Switch                           
12(2):Rated Voltage
K:Air Medium                             
D:Ground Switch
R:Fuse                                       
T:Spring Mechanism
N:Indoor                                   
125:Rated Current Of The Fuse                                          A:Derived Code
12(1):Design Number                 
31.5:Rated Short-circuit   Breaking Current(KA)          

Environmental Conditions Of Use:


1.  Ambient air temperature: -25ºC ~ +40ºC;

2.  Poster height does not exceed 1000m;

3.  The daily average relative humidity is not more than 95%, the monthly average is not more than 90%;

4.  The earthquake intensity does not exceed 8 magnitude;

5.  No fire, explosion risk, chemical corrosion and violent vibration places;

6.  Pollution level: ‖



Structural Features:

1.  Load switch, ground switch, fuse and mechanism in a frame, flexible combination, compact structure, small size, easy to install;

2.  The fracture is arranged in direct motion, the dynamic and thermal stable current parameter is high, and the operation is completed at one time;

3.  With static contact insulation cover, the ring network cabinet is isolated in the structure, eliminating the phase-to-phase insulation partition and the fracture insulation board, which can prevent the arc short circuit accident in the cabinet;

4.  With unique valve structure, after the load switch is opened, the valve will automatically isolate the fracture, and the protection performance is good;

5.  There is a reliable mechanical locking device between the load switch and the ground switch and the fuse to meet the requirements of "five defenses";

6.  There are two forms of electric operation with manual operation and AC/DC dual operation power supply, which is easy to achieve the power system: "three remote" requirements.


 The technical parameters of the form are for reference only.


Serial Number item Unit FKN12A-12D FKRN12A-12D
1 Rated voltage KV 12 12
2 Rated frequency Hz 50 50
3 Rated current A 630 125
4 Rated insulation level 1min power frequency withstand voltage To the ground, alternate KV 42 42
Isolation fracture 48 48
Lightning impulse withstand voltage (peak) To the ground, alternate 75 75
Isolation fracture 85 85
5   Load switch KA 20 -
Ground switch 20 20
6   Load switch S 4 -
Ground switch 2 2
7 Rated short circuit closing current (peak) KA 50 -
8 Rated breaking current Active load breaking current A 630 -
Closed-loop breaking current 630 -
5% active load breaking current 31.5 -
Cable charging current 10 -
Disconnect no-load transformer capacity KVA 1250 1250
9 Rated short-circuit breaking current(current limiting fuse) KA - 31.5
10 Rated transfer current A - 1200
11 Mechanical life Times 2000 2000
12 The kicker outputs power J - 1+0.5
 

When placing order, please provide the following technical parameters
1. kV rated voltage:
2. rated voltage;
3. Combination of three levels, accurate phase and accurate;
4. rated output, and the corresponding accurate level (VA).



FAQ:

1: Are you a trading company or manufacturer ?

    We are a professional factory with 7 years experience in the field of high and low voltage power transformers, substation, vacuum circuit breaker, power equipment.

2: Do you accept customized serveice ?
    We offer OEM/ODM service , can print your logo on product . our professional technical and quotation team can provice a satisfied project according to your drawing and parameters .

 
3: What is your MOQ?
    Our MOQ is 1 piece.

 
4: How long is your delivery lead time ?
    It depends on your product requirement and quantity . Generally , 5~10 working days is avaliable .

 
5: How do you solve quality problems?
    Please porvide detailed photoes of quality problems. our technical and quality testing department will analyse.we will make asatisfied soluton within 2 days .
 
6: What is the price of shipping?
    Depending upon the port of delivery, prices varies.

7: What is your payment terms ?
   30%T/T in adcance,70% before shipment . West union , L/C are also acceptable .

 
 
Model NO.:
FKN12A-12/FKRN12A-12
Arc-extinguishing Medium:
Vacuum
Installation:
Fixed
Type:
Circuit Breaker
Function:
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection, OVP(Overvoltage Protection)
Certification:
ISO9001-2000, CE, CCC
Rated Voltage:
36kv
Installation Method:
Withdrawable
Rated Current:
630A/1250A
Rated Frequency:
50/60Hz
Material:
Steel, Expoxy Resin
Mechanical Life:
10,000 Times
Certificate:
IEC CE CCC
Transport Package:
Cartons/Wooden Cases
Trademark:
KUNJI-ELECTRIC
Origin:
Zhejiang, China
HS Code:
8537209000
Production Capacity:
2000 Piece/Pieces Per Month
Package Size:
70.00cm * 40.00cm * 82.00cm
Package Gross Weight:
120.000kg